Project: ………………………………………………………………………………………..
|
||||
Daily Maintenance
check for Powerhouse Equipments
|
Date:
|
………………………………..
|
||
S.No.
|
Particulars
|
Check
|
Remarks
|
|
Power
Transformer
|
||||
1
|
Magnetic Oil Gauge
of Main Tank and Conservator Tank
|
Oil to be filled in
the transformer in case of low oil level and checked for oil leakage
|
||
2
|
Colour of Silica
Gel in the Breather
|
If silica gel
becomes pinkish, it should be replaced.
|
||
3
|
Leakage of Oil from
any point of the Transformer
|
If oil leakage is
found, required steps need to be taken to plug the leakage
|
||
Fire
Fighting
|
||||
4
|
Check Fire Service
Access
|
Ensure that fire
service access are kept clear
|
||
Diesel
Generator
|
||||
5
|
Check and inspect
lubrication oil Level
|
|||
6
|
Check leakage of
Cooling water from Radiator
|
|||
7
|
Check vibration and
Noise
|
|||
8
|
Check leakage of
Fuel Line
|
|||
Hydro
Generators
|
||||
9
|
Abnormal Noise at
Stator Core
|
check for core
looseness especially at frame joints
|
||
10
|
Wound Stator
|
Check core ,
winding temperature Cooled air and cooling system
|
||
11
|
Guide and Thrust
Bear
|
Check Bearing
Temperature wchich can be due to Abnormal Vibrations, Balancing of rotor,
Dirty Oil coolers, Cooling water flow , contaminated oil and bearing
clearances
|
||
12
|
Level Gauge on oil
level
|
Check Level Gauge
of Oil . The oil level can be high due to water leakage and low due to
leakage of oil from housing
|
||
13
|
Water leakage in
Cooler Tubes of Air Coolers
|
Check Water Leakage
in Cooler tubes and if leakage found plug the leaking tube
|
||
14
|
Air Pressure in
Pressure Gauge
|
Check air pressure
in pressure gauge and check for leakage and pipeline joints
|
||
15
|
Sparking and Mix of
Dust/ Oil in Brushes of Collector
|
Check sparking and Mix of C Dust/ oil and clean if dust found
|
||
16
|
Commutation in
Commutator Brush Gear of DC Exciter
|
Check Commutation
in commutation Brush Gear
|
||
17
|
External examination of parts of generator which are accessible
|
|||
18
|
External inspection of coolers, oil coolers, pipe lines, sealing
&control etc. for leakages
|
|||
19
|
Ensure Cleanliness of all external accessible parts of the
generator &wipe with clean & dry cloth.
|
|||
Turbine
|
||||
20
|
Temperature of bearings of the Pump-motor set
|
|||
21
|
Conditions of rubber seal of the pump and see that air is not
being sucked from here into the system
|
|||
Wednesday, August 31, 2016
Daily Maintenance Check Of Hydroelectric Powerhouse Electromechanical Equipments
Subscribe to:
Comments (Atom)